Functional Specifications
|
STANDARD RANGE |
ZERO-BASED RANGE |
||||||||||||||||
Inputs |
|
|
||||||||||||||||
Outputs |
|
|
||||||||||||||||
Air Consumption |
1.8 scfh (0.05 m3/ hr) at mid range typical |
6.0 scfh at mid range typical |
||||||||||||||||
Supply Pressure |
100 psig (6.90 BAR) max. 150 psig (10.00 BAR) max. |
100 psig (6.90 BAR) max. 150 psig (10.00 BAR) max. |
||||||||||||||||
Flow Capacity |
4.5 scfm (7.7 m3/hr) 12.0 scfm (20.0 m3/hr) 20.0 scfm (34.0 m3/hr) |
12.0 scfm (20.0 m3/hr) 20.0 scfm (34.0 m3/hr) |
||||||||||||||||
Temperature Limits |
-20° to +150° F |
-20° to +150° F |
||||||||||||||||
Impedance |
|
|
||||||||||||||||
|
|
|||||||||||||||||
|
|
|||||||||||||||||
|
|
|||||||||||||||||
|
|
Performance Specifications
|
STANDARD RANGE |
ZERO-BASED RANGE |
Linearity (Independent) |
<± 0.5% of span |
<± 1.5% of span |
Hysteresis, and Repeatability |
<0.5% of span |
<1.0% of span |
Supply Pressure Sensitivity |
<0.1% of span per 1.0 psig (0.07 BAR) |
<0.02% of span per 1.0 psig (0.07 BAR) |
RFI/EMI Effect |
<0.5% of span change in output pressure per En 61000-4-3:1998, Amendment 1, Performance Criterion A |
|
Physical Specifications
Port Sizes |
Pneumatic 1/4" NPT |
|
Media |
Clean, dry, oil-free, instrument air, filtered to 40 micron |
|
Electrical |
Conduit 1/2" NPT, Terminal Block, DIN 43650 |
|
Mounting |
Direct wall, panel, 1 1/2" pipe, DIN rail or Manifold |
|
Materials
|
Housing: Chromate-treated aluminum with epoxy paint. NEMA 4X (IP65) Elastomers: Buna-N Trim: Stainless steel; brass; zinc-plated steel |
|
Weight
|
Standard Unit; 1.3 lbs |